Local Storage seems to be disabled in your browser.
For the best experience on our site, be sure to turn on Local Storage in your browser.

Specifications of TCR-D electric actuators
The TCR-D electric actuators feature a compact design with a 90° operating angle (±2°). They include an ISO 5211 pad and star connection. The ABS plastic enclosure and steel reducing box ensure durability and efficiency. They operate in temperatures from -20°C to +60°C. Duty cycle is S4 (50% operational time), except for TCR20 and TCR40 models which have an S3 duty cycle (85% operational time).
They're available with torques from 20 Nm to 50 Nm, they support voltages of 95-265V AC/DC and 24V AC/DC.
Focus on the timer function
The TIMER function allows users to programme periodic, automatic openings and closings of a valve. The parameters for this function can be set via a menu, enabling precise control over the operation schedule. This function supports two modes: the pulse (ON/OFF) mode and the clock mode. In the pulse mode, users can set the lengths of time for which the valve remains open and closed. In the clock mode, users can specify exact times for the valve to open and close. This feature is especially useful for applications requiring regular and automated valve operations
Standard equipment of TCR electric actuators
The TCR electric actuators come with adjustable limit switches and 2 auxiliary limit switches. They feature thermal protection, a 3D position indicator, a manual override by hex key, and regulated 2-3 W anti-condensation resistor.
These actuators are equipped with an IP67 leak-tightness rating, making them suitable for indoor use and potentially for outdoor use under proper shelter.
Supporting parallel installation, the TCR-N actuators allow multiple units to operate simultaneously, which is crucial for systems requiring synchronized valve movements. Additionally, they offer manual control with a key, providing a necessary override option for maintenance or in case of power failure.
Square, star (mm) | 11 |
---|---|
Manual override | By key |
Declutchable | No |
Duty service | S4 duty service - 50% |
3D indicator | Yes |
Protection index (IP) | IP 67 |
Torque limiter | No |
ISO pad 5211 | F3/F4/F5 |
Power (W) | 15 |
Anti-condensation heater | Standard |
Positive safety | No |
Function | On-off |
Electric actuator type | TCR-02D |
Electric actuator series | TCR Series |
Operating time (s) | 10.0 |
TS max (°C) | 60 |
TS min (°C) | -20 |
Warranty period | 1 year |
Electrical connection | cable 1.5 m + gland packing M10 |